{"id":38,"date":"2019-07-04T10:57:48","date_gmt":"2019-07-04T14:57:48","guid":{"rendered":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/?post_type=chapter&#038;p=38"},"modified":"2019-10-11T14:23:10","modified_gmt":"2019-10-11T18:23:10","slug":"multi-tap-transformers","status":"publish","type":"chapter","link":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/chapter\/multi-tap-transformers\/","title":{"raw":"Multi-Tap Transformers","rendered":"Multi-Tap Transformers"},"content":{"raw":"<p class=\"no-indent\"><span>Some transformers compensate for line drop and percent voltage regulation by having multiple taps by which the volts\/turn ratio can be adjusted.<\/span><\/p>\r\n<p class=\"no-indent\">In the image below, we have a transformer whose secondary is open. For all intents and purposes, there is very little current flowing in the primary (in this case we will say it is negligible). The .25\u03a9 resistance in the primary is the resistance of the winding. In this example, the supply voltage and the terminal voltage will be the same value. There is a potential secondary voltage of 120 volts but there is no current flowing in the secondary.<\/p>\r\n\r\n\r\n[caption id=\"attachment_122\" align=\"aligncenter\" width=\"1024\"]<img src=\"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-e1566236131589-1024x494.png\" alt=\"\" width=\"1024\" height=\"494\" class=\"wp-image-122 size-large\" \/> Figure 17. Fully loaded open circuit[\/caption]\r\n<p class=\"no-indent\" align=\"left\"><span>When current flows in the secondary circuit, things start to change. Total line drop in the primary circuit is 150 V due to the volt drop across the resistance of the primary circuit (75 V+ 75 V). This means that the terminal voltage applied to the primary of the transformer is only 1050 V. With the 10:1 turns ratio on the transformer, the secondary voltage is 105 V. This is 15 V lower than is desired.<\/span><\/p>\r\n\r\n\r\n[caption id=\"attachment_124\" align=\"aligncenter\" width=\"1024\"]<img src=\"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-2-e1566236194482-1024x512.png\" alt=\"\" width=\"1024\" height=\"512\" class=\"wp-image-124 size-large\" \/> Figure 18. Fully loaded transformer[\/caption]\r\n<p align=\"left\"><span>To compensate for the line drop, it would be lovely if we could reduce the turns ratio of the transformer to 9.5:1. Some transformers provide taps to do that.<\/span><\/p>\r\n\r\n\r\n[caption id=\"attachment_125\" align=\"aligncenter\" width=\"1024\"]<img src=\"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multi-Tap20-e1566237380321-1024x751.png\" alt=\"\" width=\"1024\" height=\"751\" class=\"wp-image-125 size-large\" \/> Figure 19. Multi-tap transformer[\/caption]\r\n<ul>\r\n \t<li><span>Any increase in the number of turns in the primary will reduce the volts per turn ratio, thus lowering the secondary voltage.<\/span><\/li>\r\n \t<li><span>Any decrease in the number of turns in the primary will increase the volts per turn ratio, thus increasing the secondary voltage.<\/span><\/li>\r\n \t<li><span>The tap percentages indicate the percentage of the full turns that are effective when the tap is used.<\/span><\/li>\r\n \t<li><span>When the taps are in the primary winding, the new turns ratio can be calculated by multiplying this percentage by the full turns ratio:<\/span><\/li>\r\n<\/ul>\r\n<strong><span>Example:<\/span><\/strong>\r\n<ul>\r\n \t<li><span>Consider a 360 kVA 1200V \u2013 120V transformer.<\/span><\/li>\r\n \t<li><span>It has a turns ratio of 10:1 on the 100% tap.<\/span><\/li>\r\n<\/ul>\r\n<table style=\"width: 582px;height: 237px\" border=\"1\" width=\"575\" cellspacing=\"0\" cellpadding=\"6\">\r\n<tbody>\r\n<tr>\r\n<td style=\"width: 140.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><strong>Tap percentage<\/strong><\/div><\/td>\r\n<td style=\"width: 131.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\"><strong>Equation<\/strong><\/div><\/td>\r\n<td style=\"width: 112.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><strong>New ratio<\/strong><\/div><\/td>\r\n<td style=\"width: 130.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><strong>New secondary voltage (at 1200V)<\/strong><\/div><\/td>\r\n<\/tr>\r\n<tr>\r\n<td style=\"width: 140.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>95%<\/span><\/div><\/td>\r\n<td style=\"width: 131.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>10 x 0.95 =<\/span><\/div><\/td>\r\n<td style=\"width: 112.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>9.5:1<\/span><\/div><\/td>\r\n<td style=\"width: 130.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>126.3 V<\/span><\/div><\/td>\r\n<\/tr>\r\n<tr>\r\n<td style=\"width: 140.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>97.5%<\/span><\/div><\/td>\r\n<td style=\"width: 131.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>10 x 0.975 =<\/span><\/div><\/td>\r\n<td style=\"width: 112.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>9.75:1<\/span><\/div><\/td>\r\n<td style=\"width: 130.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>123 V<\/span><\/div><\/td>\r\n<\/tr>\r\n<tr>\r\n<td style=\"width: 140.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>100%<\/span><\/div><\/td>\r\n<td style=\"width: 131.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>10 x 1 =<\/span><\/div><\/td>\r\n<td style=\"width: 112.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>10:1<\/span><\/div><\/td>\r\n<td style=\"width: 130.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>120 V<\/span><\/div><\/td>\r\n<\/tr>\r\n<tr>\r\n<td style=\"width: 140.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>102.5%<\/span><\/div><\/td>\r\n<td style=\"width: 131.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>10 x 1.025 =<\/span><\/div><\/td>\r\n<td style=\"width: 112.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>10.25:1<\/span><\/div><\/td>\r\n<td style=\"width: 130.906px\" align=\"left\" valign=\"top\">\r\n<div align=\"left\" style=\"text-align: center\"><span>117 V<\/span><\/div><\/td>\r\n<\/tr>\r\n<\/tbody>\r\n<\/table>\r\n<h2 style=\"text-align: center\"><strong>Video Alert!<\/strong><\/h2>\r\nThis video shows how to use a multi-tap transformer to boost secondary voltage.\r\n\r\n[embed]https:\/\/youtu.be\/rVxXKvP32dQ[\/embed]\r\n<h1>Attributions<\/h1>\r\n<a href=\"https:\/\/youtu.be\/rVxXKvP32dQ\">Multi-tap transformer<\/a> video by <a href=\"https:\/\/www.youtube.com\/channel\/UCRm79BcxKhOWRj6CQAB_Cqg\">The Electric Academy<\/a> is under a <a href=\"https:\/\/creativecommons.org\/licenses\/by\/4.0\/\">Creative Commons Attribution License<\/a>.\r\n\r\n&nbsp;","rendered":"<p class=\"no-indent\"><span>Some transformers compensate for line drop and percent voltage regulation by having multiple taps by which the volts\/turn ratio can be adjusted.<\/span><\/p>\n<p class=\"no-indent\">In the image below, we have a transformer whose secondary is open. For all intents and purposes, there is very little current flowing in the primary (in this case we will say it is negligible). The .25\u03a9 resistance in the primary is the resistance of the winding. In this example, the supply voltage and the terminal voltage will be the same value. There is a potential secondary voltage of 120 volts but there is no current flowing in the secondary.<\/p>\n<figure id=\"attachment_122\" aria-describedby=\"caption-attachment-122\" style=\"width: 1024px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-e1566236131589-1024x494.png\" alt=\"\" width=\"1024\" height=\"494\" class=\"wp-image-122 size-large\" srcset=\"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-e1566236131589-1024x494.png 1024w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-e1566236131589-300x145.png 300w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-e1566236131589-768x371.png 768w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-e1566236131589-65x31.png 65w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-e1566236131589-225x109.png 225w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-e1566236131589-350x169.png 350w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><figcaption id=\"caption-attachment-122\" class=\"wp-caption-text\">Figure 17. Fully loaded open circuit<\/figcaption><\/figure>\n<p class=\"no-indent\" style=\"text-align: left;\"><span>When current flows in the secondary circuit, things start to change. Total line drop in the primary circuit is 150 V due to the volt drop across the resistance of the primary circuit (75 V+ 75 V). This means that the terminal voltage applied to the primary of the transformer is only 1050 V. With the 10:1 turns ratio on the transformer, the secondary voltage is 105 V. This is 15 V lower than is desired.<\/span><\/p>\n<figure id=\"attachment_124\" aria-describedby=\"caption-attachment-124\" style=\"width: 1024px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-2-e1566236194482-1024x512.png\" alt=\"\" width=\"1024\" height=\"512\" class=\"wp-image-124 size-large\" srcset=\"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-2-e1566236194482-1024x512.png 1024w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-2-e1566236194482-300x150.png 300w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-2-e1566236194482-768x384.png 768w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-2-e1566236194482-65x33.png 65w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-2-e1566236194482-225x113.png 225w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multitap1-2-e1566236194482-350x175.png 350w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><figcaption id=\"caption-attachment-124\" class=\"wp-caption-text\">Figure 18. Fully loaded transformer<\/figcaption><\/figure>\n<p style=\"text-align: left;\"><span>To compensate for the line drop, it would be lovely if we could reduce the turns ratio of the transformer to 9.5:1. Some transformers provide taps to do that.<\/span><\/p>\n<figure id=\"attachment_125\" aria-describedby=\"caption-attachment-125\" style=\"width: 1024px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multi-Tap20-e1566237380321-1024x751.png\" alt=\"\" width=\"1024\" height=\"751\" class=\"wp-image-125 size-large\" srcset=\"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multi-Tap20-e1566237380321-1024x751.png 1024w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multi-Tap20-e1566237380321-300x220.png 300w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multi-Tap20-e1566237380321-768x563.png 768w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multi-Tap20-e1566237380321-65x48.png 65w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multi-Tap20-e1566237380321-225x165.png 225w, https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-content\/uploads\/sites\/777\/2019\/07\/Multi-Tap20-e1566237380321-350x257.png 350w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><figcaption id=\"caption-attachment-125\" class=\"wp-caption-text\">Figure 19. Multi-tap transformer<\/figcaption><\/figure>\n<ul>\n<li><span>Any increase in the number of turns in the primary will reduce the volts per turn ratio, thus lowering the secondary voltage.<\/span><\/li>\n<li><span>Any decrease in the number of turns in the primary will increase the volts per turn ratio, thus increasing the secondary voltage.<\/span><\/li>\n<li><span>The tap percentages indicate the percentage of the full turns that are effective when the tap is used.<\/span><\/li>\n<li><span>When the taps are in the primary winding, the new turns ratio can be calculated by multiplying this percentage by the full turns ratio:<\/span><\/li>\n<\/ul>\n<p><strong><span>Example:<\/span><\/strong><\/p>\n<ul>\n<li><span>Consider a 360 kVA 1200V \u2013 120V transformer.<\/span><\/li>\n<li><span>It has a turns ratio of 10:1 on the 100% tap.<\/span><\/li>\n<\/ul>\n<table style=\"width: 582px;height: 237px; width: 575px; border-spacing: 0px;\" cellpadding=\"6\">\n<tbody>\n<tr>\n<td style=\"width: 140.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><strong>Tap percentage<\/strong><\/div>\n<\/td>\n<td style=\"width: 131.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: left;\"><strong>Equation<\/strong><\/div>\n<\/td>\n<td style=\"width: 112.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><strong>New ratio<\/strong><\/div>\n<\/td>\n<td style=\"width: 130.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><strong>New secondary voltage (at 1200V)<\/strong><\/div>\n<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 140.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>95%<\/span><\/div>\n<\/td>\n<td style=\"width: 131.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>10 x 0.95 =<\/span><\/div>\n<\/td>\n<td style=\"width: 112.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>9.5:1<\/span><\/div>\n<\/td>\n<td style=\"width: 130.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>126.3 V<\/span><\/div>\n<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 140.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>97.5%<\/span><\/div>\n<\/td>\n<td style=\"width: 131.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>10 x 0.975 =<\/span><\/div>\n<\/td>\n<td style=\"width: 112.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>9.75:1<\/span><\/div>\n<\/td>\n<td style=\"width: 130.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>123 V<\/span><\/div>\n<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 140.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>100%<\/span><\/div>\n<\/td>\n<td style=\"width: 131.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>10 x 1 =<\/span><\/div>\n<\/td>\n<td style=\"width: 112.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>10:1<\/span><\/div>\n<\/td>\n<td style=\"width: 130.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>120 V<\/span><\/div>\n<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 140.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>102.5%<\/span><\/div>\n<\/td>\n<td style=\"width: 131.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>10 x 1.025 =<\/span><\/div>\n<\/td>\n<td style=\"width: 112.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>10.25:1<\/span><\/div>\n<\/td>\n<td style=\"width: 130.906px\" align=\"left\" valign=\"top\">\n<div style=\"text-align: center; text-align: left;\"><span>117 V<\/span><\/div>\n<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2 style=\"text-align: center\"><strong>Video Alert!<\/strong><\/h2>\n<p>This video shows how to use a multi-tap transformer to boost secondary voltage.<\/p>\n<p><iframe loading=\"lazy\" id=\"oembed-1\" title=\"Multi tap transformers\" width=\"500\" height=\"375\" src=\"https:\/\/www.youtube.com\/embed\/rVxXKvP32dQ?feature=oembed&#38;rel=0\" frameborder=\"0\" allowfullscreen=\"allowfullscreen\"><\/iframe><\/p>\n<h1>Attributions<\/h1>\n<p><a href=\"https:\/\/youtu.be\/rVxXKvP32dQ\">Multi-tap transformer<\/a> video by <a href=\"https:\/\/www.youtube.com\/channel\/UCRm79BcxKhOWRj6CQAB_Cqg\">The Electric Academy<\/a> is under a <a href=\"https:\/\/creativecommons.org\/licenses\/by\/4.0\/\">Creative Commons Attribution License<\/a>.<\/p>\n<p>&nbsp;<\/p>\n","protected":false},"author":422,"menu_order":9,"template":"","meta":{"pb_show_title":"on","pb_short_title":"","pb_subtitle":"","pb_authors":[],"pb_section_license":""},"chapter-type":[],"contributor":[],"license":[],"class_list":["post-38","chapter","type-chapter","status-publish","hentry"],"part":3,"_links":{"self":[{"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/pressbooks\/v2\/chapters\/38","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/pressbooks\/v2\/chapters"}],"about":[{"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/wp\/v2\/types\/chapter"}],"author":[{"embeddable":true,"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/wp\/v2\/users\/422"}],"version-history":[{"count":11,"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/pressbooks\/v2\/chapters\/38\/revisions"}],"predecessor-version":[{"id":234,"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/pressbooks\/v2\/chapters\/38\/revisions\/234"}],"part":[{"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/pressbooks\/v2\/parts\/3"}],"metadata":[{"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/pressbooks\/v2\/chapters\/38\/metadata\/"}],"wp:attachment":[{"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/wp\/v2\/media?parent=38"}],"wp:term":[{"taxonomy":"chapter-type","embeddable":true,"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/pressbooks\/v2\/chapter-type?post=38"},{"taxonomy":"contributor","embeddable":true,"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/wp\/v2\/contributor?post=38"},{"taxonomy":"license","embeddable":true,"href":"https:\/\/pressbooks.bccampus.ca\/singlephasetransformers\/wp-json\/wp\/v2\/license?post=38"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}