Electrical Terms and Definitions
2 Overload and Overcurrent Terms
Click play on the following audio player to listen along as you read this section.
https://video.bccampus.ca/id/0_228kq28a?width=608&height=70&playerId=23448552
Inrush Current
When a motor load is first started, before it has a chance to pick up speed and begin to rotate, the characteristics of the stator coil are that of a short circuit. As such the motor starts to draw very high values of current. This current creates a magnetic field that causes the motor shaft to spin, and that spinning action creates a counter-EMF (CEMF), which limits the current to its normal running value.
The initial high value of current is called inrush current and can cause severe line disturbances and nuisance tripping if fuses and circuit breakers are not sized accordingly.
Overload
The term “overload” describes a moderate and gradual rise in the value of current over a relatively long period of time. It is caused by excessive amounts of current drawn by a motor, which may be as high as six times the rated current. This is caused by too much load on a motor. Systems are protected by overload protection relays. While overloads are allowed for a short time (usually minutes), prolonged overloads will use thermal action to cause a protective device to trip.
Overcurrent
The term “overcurrent” (sometimes called a short circuit or a ground fault) describes a sharp and fast rise in current over a very short period of time (fractions of a second). Circuits and equipment are protected from overcurrent situations by fuses or circuit breakers.
During a short circuit the value of current is far greater than the nominal line current and can indeed be anywhere from six times to many hundreds of times greater the normal rated current value of circuit.
There are several causes of overcurrent situations. For example, when a bolted fault occurs—either a line to ground or a line to line fault. This causes a very large value of current to be drawn because of the inversely proportional relationship between the resistance of a circuit and the current that is drawn.
Another less intuitive cause of short circuits is when an induction motor starts. When a three-phase induction motor is first energized, the stator windings consist of a very low resistance path. This draws a very large inrush current which is indistinguishable from a standard short circuit, except that it quickly drops down to the rated value of current drawn by the motor. This is due to the CEMF (counter-electromotive force) developed by the rotating shaft of the motor. When the motor is spinning, a CEMF limits the current to safe values. When the motor is not spinning, a very large value of current is drawn from the source. This current is sometimes called locked-rotor current, and motor starters and overcurrent devices must be rated to safely handle and interrupt this value of current.
Effects of short circuits
Overcurrents are responsible for two main negative effects:
- Thermal energy: High values of current will create large amounts of heat, which can damage equipment and wires. Thermal energy can be expressed by the formula: I2t (current squared multiplied by time) meaning that the longer the fault persists, the greater the potential thermal damage.
- Mechanical forces: Large fault currents can create powerful magnetic fields, and exert huge magnetic stress on busbars and equipment, sometimes warping them out of shape and creating new problems in the process.
Large values of fault current can cause severe damage to circuits and equipment, so overcurrent protective devices must act very quickly to clear the fault. There are two main categories of overcurrent protective devices: fuses and circuit breakers.
Text Attributions
- This chapter was adapted from “Overload and Overcurrent Protection” in Basic Motor Control by Chad Flinn and Aaron Lee, which is under a CC BY 4.0 Licence. Adapted by Aaron Lee.
The rate of flow of an electric charge, measured in amperes (or amps). When one coulomb of charge moves past one point in once second, current is said to flow at a rate of one ampere. Current flows from negative potential to a positive potential through a load.
The initial high value of current produced when an inductive load is first energized.
An insulated tube containing a strip of conductive metal that has a lower melting point than either copper or aluminum. It protects a circuit from damage because it will melt in overload or overcurrent situations and break the connection with the rest of the circuit.
An automatic device that is designed to safely disconnect circuits under fault conditions. Most circuit breakers provide Overload and Overcurrent protection, and are rated in Volts, Amps and Horsepower.
A moderate and gradual rise in the value of current over a relatively long period of time that is caused by excessive amounts of current drawn by a motor due to too much load being put on the motor.
A moderate and gradual rise in the value of current over a relatively long period of time that is caused by excessive amounts of current drawn by a motor due to too much load being put on the motor.
A sharp and fast rise in current over a short period of time (fractions of a second) where the value of current is far greater than the nominal line current.
The opposition to the flow of current in an electric circuit, measured in ohms (Ω).
The current drawn by a motor when the motor is not spinning.
Fuses and or circuit breakers that are designed to protect wires and equipment in the event of a fault.